A loop—or “sensing loops” as they are commonly referred to— is made from a continuous run of wire with no splices, which is typically wound in a rectangular shape and saw-cut into the existing pavement. In some instances, prefabricated or “pre-formed” loops can be installed before paving or pouring concrete on the roadway. The ends of the wire are brought back to the gate operator and attached to a loop detector. The lead-in or “home run” from the corner of the loop to the detector must be twisted a minimum of five times per foot. The detector powers the loop, causing a magnetic field around the wire. The loop then tunes to a resonate frequency, and the detector constantly monitors the frequency for changes. When a vehicle enters the loop, the frequency increases causing the detector to send an output to the gate operator. Size Matters
The height of detection is equal to approximately two-thirds the length of the short side of the loop. For example, a 4-foot-by-8-foot loop will give a detection height between 2 1/2 and 2 3/4 feet. For high-bed vehicle detection, the typical loop size is 6 feet by 8 feet. The number of turns in the loop is determined by the size of the loop. Multiplying the length by the width will give you the loop area in square feet. A loop area of 12 to 60 square feet requires four turns. An area of 60 to 240 square feet requires three turns. Adding turns to a loop does not increase the sensitivity, but will make the loop more stable if the lead-in is longer than 400 feet. The size of the loop also determines the loop placement. The larger the loop, the greater the spacing must be between the loop and the gate. Essentially, loops should be placed a minimum of 4 feet from the gate.
It’s important to use the correct wire in your loop installation. A 14, 16 or 18 AWG stranded wire can be used. The insulation on the wire should be XLPE (cross-linked polyethylene). This insulation has a high resistance to water, heat, abrasions, oils and gasoline, each of which can cause false detections. The Installation
Finally, when using more than one loop detector in the same installation (i.e. a reversing loop and a free exit loop), the frequency settings on the detectors should be set differently to avoid “cross-talk” which can cause false detections. Wire connections are also critical to the installation procedure. Whenever possible, the connections should be soldered together instead of using a wire nut or crimp connector. Loose connections can cause false detections and, over time, may show signs of corrosion. The Meter Solution
Most loop detectors have builtin diagnostics which can identify problems in the detection system. A series of blinking LED’s is an indication of possible loop problems. If this occurs, the detector must be reset to continue normal operation of your system. Full diagnostic detectors are available for problem sites. These units can keep track of shorts or intermittent problems that may temporarily correct themselves, and should help determine the condition of the loop. A Guide to Common Loops The following types of loops are commonly used: Reversing Loop: Used to stop or reverse direction of an automatic gate or barrier operator.Free Exit (Egress) or Free Entry (Ingress): Used to open an automatic gate or raise the arm of a barrier operator.Shadow Loop: Used in swing gate applications. This loop is placed inside the swing area of the gate, is only active when the gate is in the full open position, and will not allow the swing gate to close.Close Loop: Used in barrier operator applications. This loop is placed directly under the arm of the operator. When the vehicle clears the loop, the arm automatically lowers.Arming loop: Used to control access to a site. The vehicle must drive onto the arming loop before using an access device such as a transmitter or card.